GAS OPERATION |
Primary Symptom |
Secondary Symptom |
Cause |
Cure |
When switching on from cold no indicator lights come on
|
|
Reversed power supply |
Check connection from caravan wiring to wall switch |
Power not reaching heater |
Check wiring from wall switch to caravan supply |
Fuses not in place or blown |
Check for wiring fault and replace fuse |
When switching on from cold green light only comes on and stays on. |
Heater does not operate
No fail light. Igniter not working. Gas valve not working |
Multi-pin plug
disconnected at wall switch or heater. |
Re-connect multi-pin plug |
| When switching on from cold green & yellow lights come on |
Heater does not operate
Battery condition low causing pump to run slowly. |
Voltage at wall switch below 10.5v |
Charge up caravan battery |
When switching on, green light comes on and after 10 seconds the red as well . |
When listening to the heater during this sequence a click should be heard followed by intermittent ticking for 10 seconds. |
Air in gas supply pipe
|
Purge pipe by switching off and on again. Repeat if necessary |
| No gas supply |
| Incorrect gas pressure |
| Intake of flue obstructed |
Check isolation valves & bottle |
| Water coming from cowl |
Pump pressure too high |
|
| A click heard but no ticking or ticking but no click |
Poor connection at multi-pin plug in wall switch or on heater |
Check and clear |
| |
| Pull out arid reinsert plugs |
Yellow light comes on when pump is operated
|
Pump runs slowly |
Low battery voltage or inadequate pump wiring |
Check and charge battery, If not successful. Check wiring. |
| Red light comes on after about 30-45 mins. with water and steam from cowl. |
No continuous water flow from cowl when pump as running |
Pressure relief valve operating on temperature rise |
Pump pressure too high |
| Continuous water flow from cowl when pump is operated |
Fusible plug blown indicating thermostat failure |
Do not continue to use heater Seek service attention. |
| MAINS ELECTRIC OPERATION |
| Mains immersion heater does not operate
|
Indicator light on isolating switch not alight |
Caravan not connected to site supply |
Connect |
| RCD in caravan tripped |
Reset and try again. If not successful seek service attention. |
| Site supply not adequate |
Switch off. Seek warden attention. |
Indicator light on isolating switch alight |
Thermostat
|
Switch off and seek service attention.
|
| Over temp. thermostat |
Reset button. |